Articles / 4 min read
Textile boilers: planning coal for winter gas cuts in Faisalabad
Textile boiler coal for a 10 t/h boiler comes to about 29 tonnes of Duki lump a day, close to one 25 tonne truck every day, on the assumptions below. A mill in Faisalabad or Lahore that runs steam on gas should fix that number, the coal size and the ash plan before a gas cut forces the switch.

Gas against coal per unit of heat
A mill that depends on utility gas for steam either stops or scrambles when supply is cut. Gas has also become dearer for captive power: the Off the Grid levy law raises the levy in steps, the last to 20% in August 2026.
ARY News reported in April 2026 that captive gas had gone from Rs 4,743 to Rs 4,906 per mmBtu, and the levy from Rs 1,243 to Rs 1,406. For many mills coal for steam now makes sense on cost as well as supply.
| Fuel | Price | Heat | Rs per 1,000 kcal |
|---|---|---|---|
| Captive gas (ARY, April 2026) | Rs 4,906 per mmBtu | 252,000 kcal per mmBtu | 19.5 |
| Captive gas plus levy, if the levy is on top | Rs 6,312 per mmBtu | 252,000 kcal per mmBtu | 25.0 |
| Duki lump delivered | Rs 51,750 a tonne | 6,000 kcal/kg | 8.6 |
| Duki run-of-mine delivered | Rs 47,000 a tonne | 5,500 kcal/kg | 8.5 |
Which coal for which boiler
A chain grate (travelling grate) boiler burns coal in a bed on a moving grate and wants sized coal with little dust; fines fall through or pack the bed so air cannot pass. Duki lump or Chamalang lump broken to the size your boiler maker specifies is the usual choice. Tell us the size range and we match it at loading.
A fluidised bed (FBC) boiler burns crushed coal suspended in hot sand or ash and forgives fuel quality: run-of-mine, crushed lump and a share of fines can all work, and limestone in the bed captures much of the sulphur. For FBC, Duki run-of-mine at about Rs 34,000 a tonne ex-Quetta, or a blend with fines at about Rs 25,000, often gives the lowest cost per unit of steam. Hand-fired and pulverised fuel plants have their own sizing; ask us. Prices are indicative and confirmed when you contact us.

How much coal the boiler burns
We assume 580 kcal to turn a kg of feedwater at 80 degrees C into steam at 10 bar, and that the boiler puts 80% of the coal's heat into steam, a fair figure for a well run coal boiler. Your maker's data will be better, and our boiler coal consumption calculator lets you change both. A boiler on part load or at lower efficiency burns more.
- 5 t/h boiler14.5 tonnes a day
- 10 t/h boiler29 tonnes a day
- 20 t/h boiler58 tonnes a day
Steam per hour times 580 kcal per kg, divided by 6,000 kcal/kg times 0.80 efficiency, times 24 hours. One 25 tonne truck a day is about 29 tonnes, so a 10 t/h boiler takes about 8.1 trucks a week.
Sulphur and ash
Balochistan coal carries 3 to 6% sulphur; Sor Range is near 3% and Mach / Harnai near 6%. In the flue gas, sulphur turns to acid if it cools too far and eats economisers, air heaters and chimneys. Keep the exit temperature above your maker's minimum, especially on cold Punjab mornings, and choose Sor Range if the boiler has no sulphur control.
Ash is what is left. At the ash on our sheet, a tonne of Duki lump leaves about 150 kg, run-of-mine about 200 kg and fines about 250 kg, so a boiler burning 29 tonnes of lump a day has about 4.3 tonnes of ash to remove every day. Plan who removes it each shift, and where it goes, before the first truck arrives.
Storage and ordering rhythm
Delivery from Quetta to Punjab takes 2 to 3 days once loaded, but roads, weather and a busy season add days. Keep two to three weeks of coal on hard, drained ground in compact piles, lump and fines apart, oldest coal first; tall loose heaps left for months heat up and smoulder. A fixed number of 25 tonne trucks a week with the price agreed per truck before loading works better than panic buying. Call or WhatsApp us on 0349 4384514 to set that up; we supply Balochistan coal from Quetta and Sindh coal from the mines near Hyderabad.
Questions people ask
Does high sulphur coal damage boilers?
It can, if the flue gas cools enough for acid to form on the economiser and air heater. Keep the exit temperature up, choose lower sulphur coal, or use limestone in an FBC bed.
Can fluidised bed boilers burn coal fines?
Yes. FBC boilers take crushed coal and a share of fines, which makes them cheaper to fuel than chain grate boilers.
Prices are indicative, per tonne, excluding sales tax, and change week to week. See today's sheet or ask us for a confirmed price.